Babcock-Davis Acoustical smoke vents are a rooftop venting system that automatically opens - releasing heat, smoke, and noxious fumes during a fire. Each smoke vent will open automatically when a fusible link inside the vent reaches its melting temperature. Smoke vents are spring-operated to open against a 10 psf snow load. (Comes standard in red oxide, shown in custom colors ArcticWhite-exterior and TheatreBlack-interior.)

Acoustical smoke vents feature:
- Innovative, upward opening, single-layer door construction.
- Energy-efficient R13 insulation for optimal envelope performance.
- Acoustical ratings to STC 45 & OITC 37.
- UL793 Listed and FM 4430 Approved
|
|


Quick Spec
Cover & Liner 14 gauge galvanized steel cover is stiffened to withstand a live load of 40 psf
12 gauge galvanized steel liner
Curb 14 gauge galvanized steel, 13" high curb, double wall, 4.75" mounting flange, 0.50" diameter mounting holes
Latch Zinc-plated steel tandem pyrolatches with 165F fusible link, interior and exterior manual pull handles
Spring/Hinge Zinc-plated steel heavy duty tamper proof spring and hinge pack designed to automatically open vent against a 10psf snow load.
Insulation 3" rigid insulation in cover and at curb perimeter
Finish Red oxide powder coat |